FAN PERFORMANCE (cont.)
Table 49 – PULLEY ADJUSTMENT
UNIT
MOTOR/DRIVE
COMBO
MOTOR PULLEY TURNS OPEN
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
04
3
phase
Medium Static 1251 1208 1165 1121 1078 1035 992 949 905 862 819
High Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035
05
3
phase
Medium Static 1303 1265 1226 1188 1150 1112 1073 1035 997 958 920
High Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035
06
3
phase
Medium Static 1380 1349 1317 1286 1254 1223 1192 1160 1129 1097 1066
High Static 1639 1596 1553 1510 1467 1424 1380 1337 1294 1251 1208
07
3
phase
Standard Static 747 721 695 670 644 618 592 566 541 515 489
Medium Static 949 927 906 884 863 841 819 798 776 755 733
High Static 1102 1083 1063 1044 1025 1006 986 967 948 928 909
08
3
phase
Standard Static 733 712 690 669 647 626 604 583 561 540 518
Medium Static 936 911 887 862 838 813 788 764 739 715 690
High Static 1084 1059 1035 1010 986 961 936 912 887 863 838
09
3
phase
Standard Static 652 633 614 594 575 556 537 518 498 479 460
Medium Static 838 813 789 764 739 715 690 665 640 616 591
High Static 1084 1059 1035 1010 986 961 936 912 887 863 838
12
3
phase
Standard Static 609 592 575 558 541 525 508 491 474 457 440
Medium Static 757 736 715 694 673 652 631 610 589 568 547
High Static 963 943 923 903 883 863 842 822 802 782 762
NOTE: Do not adjust pulley further than 5 turns open.
--- F a c t o r y s e t t i n g s
* Do not set motor pulley above 5 turns open for A or AX section belts
** Do not set motor pulley below 1 turn open for B or BX section belts
50HCQ