Table 3 – MINIMUM -- MAXIMUM AIRFLOWS ELECTRIC HEAT
UNIT
COOLING ELECTRIC HEATERS
MINIMUM MAXIMUM MINIMUM MAXIMUM
50HCQA04 900 1500 900 1500
50HCQA05 1200 2000 1200 2000
50HCQA06 1500 2500 1500 2500
50HCQA07 1800 3000 1800 3000
50HCQD08 2250 3750 2250* 3750
50HCQD09 2550 4250 2552* 4250
50HCQD12 3000 5000 3000* 5000
*Minimum electric heat CFM exceptions :
UNIT UNIT VOLTAGE HEATER kW
UNIT
CONFIGURATION
REQUIRED MINIMUM
CFM
50HCQD08
50HCQD09
575
17.0
Horizontal or Vertical
2800
34.0 2350
50HCQD12
230
50.0
Vertical 3550
Horizontal 3420
43.5 Horizontal or Vertical 3040
575
50.0
Vertical
3150
33.5
3520
Horizontal 3420
26.5 Vertical 3610
Table 4 – SOUND PERFORMANCE TABLE
50HCQ
OUTDOOR SOUND (dB)
A --- W E I G H T E D 63 125 250 500 1000 2000 4000 8000
A04 76 51.8 69.0 64.6 67.8 70.7 63.8 60.9 59.0
A05 79 56.1 69.6 68.7 72.5 72.8 68.9 65.0 61.2
A06 79 57.7 66.6 68.7 72.9 74.5 71.1 67.6 62.6
A07 81 86.7 82.7 79.1 78.4 75.4 71.2 67.8 62.9
D08 83 87.3 81.6 79.7 80.6 79.0 73.5 69.2 66.1
D09 87 61.7 74.7 77.4 82.6 84.9 81.9 78.8 75.9
D12 83 61.0 67.3 75.1 77.7 78.1 75.5 71.2 66.7
LEGEND
dB --- Decibel
NOTES:
1. Outdoor sound data is measured in accordance with
AHRI standard 270---95.
2. Measurements are expressed in terms of sound power.
Do not compare these values to sound pressure values
because sound pressure accounts for specific environ-
mental factors which do not match individual applica-
tions. Sound power values are independent of the envir-
onment and therefore more accurate.
3. A ---weighted sound ratings filter out very high and very
low frequencies, to better approximate the response of
an “average” human ear. A ---weighted measurements for
Carrier units are taken in accordance with 270---95.