47
Table18–PremierLinkControllerSensorUsage
APPLICATION
OUTDOOR AIR
TEMPERATURE
SENSOR
RETURN AIR
TEMPERATURE
SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
RETURN AIR
ENTHALPY SENSOR
Differential Dry Bulb
Temp era tur e w ith
PremierLink
(PremierLink requires
4 --- 2 0 m A A c t u a t or )
I n c l u d e d ---
CRTEMPSN001A00
R e q u i r e d ---
33ZCT55SPT
or equivalent
--- ---
Single Enthalpy with
PremierLink
(PremierLink requires
4 --- 2 0 m A A c t u a t o r )
I n c l u d e d ---
Not Used
---
R e q u i r e s ---
33CSENTHSW
---
Differential Enthal py
with PremierLink
(PremierLink requires
4 --- 2 0 m A A c t u a t o r )
I n c l u d e d ---
Not Used
---
R e q u i r e s ---
33CSENTHSW
R e q u i r e s ---
33CSENTSEN
NOTES:
CO
2
Sensors (Optional):
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 --- Aspirator b ox used for duct---mounted CO
2
room sensor.
33ZCT55CO2 --- Space temperature and CO
2
room sensor with override.
33ZCT56CO2 --- Space temperature and CO
2
room sensor with override and setpoint.
Table 19 Space Sensor Mode
TB1 TERMINAL FIELD CONNECTION INPUT SIGNAL
1 T 5 5 --- S E N / T 5 6 --- S E N Analog (10k thermistor)
2 RMTOCC Discrete, 24VAC
3 T 5 5 --- S E N / T 5 6 --- S E N Analog (10k thermistor)
4 CMPSAFE Discrete, 24VAC
5 T56---SET Analog (10k thermistor)
6 FSD Discrete, 24VAC
7 LOOP---PWR Analog, 24VDC
8 SFS Discrete, 24VAC
9 IAQ---SEN A n a l o g , 4 --- 2 0 m A
10 FILTER Discrete, 24VAC
11 I A Q --- C O M / O A Q --- C O M / R H --- C O M A n a l o g , 4 --- 2 0 m A
12 CCN + (RED) Digital , 5VDC
13 OAQ ---SEN/RH---SE N A n a l o g , 4 --- 2 0 m A
14 CCN Gnd (WHT) Digital, 5VDC
15 A UX OUT (Po wer Exhaust) (Output) Discrete 24VAC
16 CCN --- (BLK) Digital, 5VDC
LEGEND:
T 5 5 --- S p a c e Te m p e r a t u r e S e n s o r F S D --- F i r e S h u t d o w n
T 5 6 --- S p a c e Te m p e r a t u r e S e n s o r I A Q --- I n d o o r A i r Q u a l i t y ( C O
2
)
CCN --- Carrier Comfort Network
R
(communication bus) OAQ --- Outdoor Air Quality (CO
2
)
C M P S A F E --- C o m p r e s s o r S a f e t y R H --- R e l a t i v e H u m i d i t y
F I LT E R --- D i r t y F i l t e r S w i t c h S F S --- S u p p l y Fa n S t a t u s

Table of Contents