51
SEN J5-2
J5-3
COM
13
11
TB1
TB1
PL
OAQ Sensor/RH Sensor
24 VAC
C08275
Fig. 61 -- Outdoor CO
2
Sensor Connections
Space Relative Humidity Sensor or Humidistat
Connections —
Space Relative Humidity Sensor connections: The
access o ry space humidity sens o r (33ZC S EN S R H -0 1) is
installed on an interio r wall to measur e the relative humidity
of the air within the occupied s pace.
The use of a standard 2 X 4 inch ele ctrical box to
accommodate the wiring is recommended for installation.
The sensor can be mounted directly on the wall, if
acceptable by local codes.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
permanent damage to the sensor.
DO NOT cle an or touch the sensing element with
chemical solvents as they can permanently damage
the sensor.
CAUTION
!
IMPORTANT: DO NOT mount the sensor in drafty
areas such as near heating or air--conditioning ducts, open
windows, fans, or over heat sources such as baseboard
heaters, radiators, or wall--mounted dimmers. Sens ors
mounted in those areas will produce inaccurate readings.
If the sens o r is ins talled directly on a wall, install the
humidity sensor using 2 screws and 2 hollow wall anchors
(field supplied). Do not over tighten screws. See Fig. 62.
SW2
12345 6
ON
Io
Vin
Gnd
Vo
MOUNTING
HOLES
WIRING
OPENING
C11084
Fig. 62 -- Space Relative Humidity Sensor Installation
The sensor must be mounted vertical ly on the wall. The
Carrier logo should be orientated correctly when the
sensor is properly mounted.
Avoid corner locations. Allow at least 4 ft between the
sensor and any corner. Airflow near corners tends to be
reduced, resulting in erratic sensor readings. The sensor
should be vertically mounted approximately 5 ft up from
the floor, beside the space temperature sensor.
For wiring distances up to 500 feet, use a 3--conductor, 18
or 20 AWG cable. A CCN communication cable can be
used, although the shield is not required. The shield must
be remove d from the sensor end of the cable if this cable
is used. See Fig. 63 for wiring details.
Io VoVin Gnd
BLACK
RED
TB1-7
TB1-13
C11180
Fig. 63 -- Space Relative Humidity Sensor Connection
The power for the sensor is provided by the PremierLinkt
controller on terminal J5--4 (+33 to +35vdc).
To wire the sensor:
1. At the sensor, remove 4 inches of the jacket from the
cable. Strip ¼ inch of insulation from each conductor.
Route the cable through the wire clearance opening in
the center of the sensor. See Fig. 62.
2. Connect a field --supplied BLACK wire to the sensor
screw terminal marked Vin.
3. Connect a field--supplied RED wire into the sensor
screw terminal marked Io.
4. Connect the field--supplied RED wire from the sensor
to TB1--13.
5. Connect the field--supplied BL ACK wire from the
sensor to TB1--7.
Smoke Detector/Fire Shutdown (FSD) —
This function is available only when PremierLinkt
controller is configured for (Space) Sensor Mode. The unit
is factory--wired for PremierLink FSD operation when
PremierLink controller is factory--installed.
On 50HC units equipped with factory--instal led Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is i nitiated via the
smoke detector’s Alarm NO contact set. The PremierLink
controller comm unicates the smoke detector’s tripped
status to the CCN building control. See Fig. 50 and 51, the
PremierLink controller wiring diagrams.