Electrical Wiring
Signal wiring drawing
Outdoor units have parallel connections via three lines with polarity. The main unit, central control, and all indoor units
have parallel connections via two lines without polarity.
There are three connecting ways between the line control and indoor units:
A. One wired controller controls multiple units, i.e. 2-16 indoor units, as shown in the above gure(1-5 indoor units).
The indoor unit 5 is the line-controlled master unit and others are the slave units. The remote controller and the
master unit(directly connected to the indoor unit of wired controller) are connected via three lines with polarity. Other
indoor units and master unit are connected via two lines or three lines with polarity (If the PCB of indoor is DC, the
wired controller needs to be connected to ABC, while the PCB of indoor is AC, the wired controller only connects to
BC). SW01 on the mater unit of line control is set to 0 while SW01 on the slave units of line control are set to 1,2,3
and so on in turn.(Please refer to the code setting page).
B.One wired controller controls one indoor unit, as shown in the above gure (indoor units 6–19). The indoor unit and
the wired controller are connected via three lines with polarity.
C.Two wired controllers control one indoor unit, as shown in the gure (indoor unit 20). Either of the controllers can
be set to be the master controller while the other is set to be the auxiliary controller. The master wired controller and
indoor units, and the master and auxiliary wired controller are connected via three lines with polarity.
19
outdoor 1 outdoor 2 outdoor 3
communication wire with polarity
Indoor 1 (AC) Indoor 2 (AC) Indoor 3 (DC)
control wire for wired controller
with polarity
Indoor 4 (DC)
Indoor 5 (Master DC
or AC)
Indoor 6 Indoor 7 Indoor 8 Indoor 9 Indoor 10
Indoor 11 Indoor 12 Indoor 13 Indoor 14 Indoor 15
Indoor 16 Indoor 17 Indoor 18 Indoor 19 Indoor 20
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
wired
controller
.
.
.