Test Run & Fault Code
• Before switching on the unit, test the supply terminal tier (L, N terminals) and grounding points with 500V megaohm
  meter and check if the resistance is above 1MΩ. The unit cannot be operated if it is below 1MΩ.
• Connect the unit to the power supply of the outdoor units to energize the heating belt of the compressor. To protect the
  compressor at start-up, power it on 12 hours prior to the operation.
• Review the test run procedures in the outdoor unit and ensure that the outdoor unit has been properly installed
  according to the instructions in the outdoor manual.
Check that all piping has been installed, connected and insulation in accordance with the instructions provided 
in the manual.
Ask the installation personnel to conduct a test run. Conduct the testing procedures according to the manual and check if 
the temperature regulator works properly.
When the machine fails to start due to the room temperature, the following procedures can be undertaken to conduct 
compulsive running. This function is not provided for the type with remote control.
• Set the wired controller to cooling/heating mode, press ‘ON/OFF’ button for 5 seconds to enter into the compulsive
  cooling/heating mode. Press the ‘ON/OFF’ button again to quit compulsive running and stop the operation of the air
  conditioner.
When any fault appears, consult the fault code of the wired control or the ashing times for LED5 on the indoor unit 
board, and nd the faults as shown in the following table to troubleshoot.
Indoor unit faults
Before test run
Test run method
Fault remedies
 check if the mains voltage matches
 check if there is leakage at the piping joints
 check if the connections of mains power and indoor & outdoor
   units are correct
 check if the serial numbers of the terminals match
 check if the installation place meets requirements    
 check if there is too much noise
 check if the connecting line is fastened
 check if the connectors for tubing are heat insulated 
 check if the water drains outside
 check if the indoor units are positioned