What are ZS sensors?
ZS Sensors Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation Guide All rights reserved
7
Rnet wiring specifications
The Rnet communicates at a rate of 115 kbps and should be wired in a daisy-chain, star, or hybrid configuration.
NOTE
Use the specified type of wire and cable for maximum signal integrity.
Description 4 conductor, shielded or unshielded, CMP, plenum rated cable
Conductor 22 AWG (7x0096) bare copper
Maximum length 500 feet (152 meters)
Insulation Low-smoke PVC (or equivalent)
Color Code Black, white, green, red
Shielding If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire
UL temperature rating 32–167°F (0–75°C)
Voltage 300 Vac, power limited
Listing UL: NEC CL2P, or better