EasyManua.ls Logo

Carrier ZS - ZS Outdoor Air Temperature Sensors; Specifications for ZS Outdoor Air Sensors

Carrier ZS
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ZS outdoor air temperature sensors
ZS Sensors Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation Guide All rights reserved
33
ZS outdoor sensors measure temperature or temperature/humidity.
Outdoor Temperature
Sensor
Outdoor Temperature/Humidity Sensor
Bottom probe only
Specifications for ZS outdoor air sensors
Sensing element
Temperature Range:
Accuracy:
-40° to 158°F (-40° to 70°C)
±1.3°F (0.72°C)
Humidity Range:
Accuracy:
10% to 90%
±2.0% typical at less than 0.5% drift per year. Calibrated at 73.4°F
(23°C).
Sensor
Temperature Range:
Accuracy:
20° to 120°F (-5° to 50°C)
±0.9°F (0.5°C)
Humidity Range:
Accuracy:
10% to 90%
±2.0% typical at less than 0.5% drift per year. Calibrated at 73.4°F
(23°C).
Enclosure material Polycarbonate, UL94V-0
Enclosure rating NEMA 4, IP66, UV rated