Condensing Pool Heater Genie S
Minimum Distance mm
A Directly below an opening, air brick, opening window etc. 300
B Above an opening, air brick, opening window etc. 300
C Horizontally to an opening, air brick, opening window etc. 300
D Below a gutter or sanitary pipework 75
E Below the eaves 200
F Below a balcony or carport roof 200
G From vertical drain or soil pipework 150
H From an internal or external corner 300
I Above ground, roof or balcony level 300
J From a surface or a boundary line facing a terminal 600
K From a terminal facing a terminal (Horizontal fl ue) 1200
K From a terminal facing a terminal (Vertical fl ue) 600
L From a opening in a carport (e.g. door, windows) into the building 1200
M Vertically from a terminal on the same wall 1500
N Horizontally from a terminal on the same wall 300
R From an adjacent wall to fl ue (Vertical only) 300
S From an adjacent opening window (vertical only) 1000
T Adjacent to windows or openings on pitched and fl at roofs 600
U Below windows or opening on pitched roofs 2000
Fig. 1.0
5
Flue terminal positions