45
GB
CN
GR
FR
SP
PT
Flue duct terminal
Coaxial
V
ertical two-pipe
Horizontal two-pipe
Outer
duct
diameter
100
mm
80 mm
80 mm
Max. length
of flue duct
5
m
15 m
30 m
Each 90° bend
reduces the duct
max. length by
1 m
0,5 m
0,5 m
Each 45° bend
reduces the duct
max. length by
0,5 m
0,25 m
0,25 m
Flue
terminal
diameter
100
mm
133 mm
-
Figure 6
Boiler size
2.24 CF 2.24 FF
Installation of flue and air ducts
(2.24 CF)
We guarantee ease and exibility of installation for a gas-red forced draft boiler thanks
to the ttings and xtures supplied (described below).
The boiler is especially designed for connection to an exhaust ue / air ducting, with
either coaxial, vertical or horizontal terminal. By means of a splitting kit a two-pipe system
may also be installed.
Exclusively
install fittings supplied by the manufacturer.
Figure 7
020221_1200
securing clamp
seal
r
estrictor (*)
Figure 8
...coaxial flue - air duct (concentric)
This type of duct allows to disengage exhaust gases and to draw combustion air both
outside the building and in case a LAS ue is tted.
The 90° coaxial bend allows to connect the boiler to a ue-air duct in any direction as it
can rotate by 360°. It can moreover be used as a supplementary bend and be coupled
with a coaxial duct or a 45° bend.
(*) The restrictor must be removed in case the ue duct length exceeds 1 m.
If the ue outlet is placed outside, the ue-air ducting must protrude at least 18mm out
of the wall to allow alluminium weathering tile to be tted and sealed to avoid water
leakages.
Ensure a minimum downward slope of 1 cm towards the outside per each metre of
duct length.
A 90° bend reduces the total duct length by 1 metre.
A 45° bend reduces the total duct length by 0.5 metre.
0609_0705 / CG_1792
0503_0904 / CG_1636
0503_0905 / CG_1638