EasyManuals Logo

Chigo CSQ4-300R User Manual

Chigo CSQ4-300R
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
CHIGO CAC FCU MCAC-VTSM-2008-09
Błąd! Nie mna odnaleźć źródła odwania.
6. Wiring
Caution:
1. The air conditioner should use separate power supply with rated voltage.
2. The external power supply to the air conditioner should have ground wiring, which is linked to the
ground wiring of the indoor and outdoor unit.
3. The wiring work should be done by qualified persons according to circuit drawing.
4. An all-pole disconnection switch having a contract separation of at least 3mm in a pole should be
connected in fixed wiring.
5. Be sure to locate the power wiring and the signal wiring well to avoid cross-disturbance.
6. Do not turn on the power until you have checked carefully after wiring.
Note:
Remark per EMC Directive 89/336/EEC to prevent flicker impressions during the start of the compressor
(technical process), following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. The
distribution has to be of a low impedance, normally the required impedance reaches at a 32 A fusing
point.
2. No other equipment has to be connected with this power line.
3. For detailed installation acceptance please refer to your power supplier, if restrictions do apply for
products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner refer to the rating plate of the product.
5. For any question contact your local dealer.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Chigo CSQ4-300R and is the answer not in the manual?

Chigo CSQ4-300R Specifications

General IconGeneral
BrandChigo
ModelCSQ4-300R
CategoryAir Conditioner
LanguageEnglish

Related product manuals