E.SPO
Output side phase 
loss
Output UVW has phase loss
Check output wiring
error code
Fault type
Possible cause of failure
Countermeasures
E.OV2
Inverter 
deceleration 
running over 
voltage
1. Motor short circuit to ground
Check motor connection
2. Potential energy load or load inertia 
    torque is large
plus suitable dynamic braking 
components
3. The deceleration time is too short Extend deceleration time
E.OV3
Inverter 
running at 
constant speed 
overvoltage
1. Motor short circuit to ground
Check motor connection
2. During vector control, the ASR parameter 
    setting is improper
Set appropriate ASR parameters
3. The acceleration and deceleration time 
    setting is too short
Appropriately extend the acceleration 
and deceleration time
4. Abnormal input voltage
Check input power
5. The input voltage fluctuates abnormally
Install input reactor
6. Large load inertia
plus suitable dynamic braking 
components
E.SPI
Input side phase 
loss
Input RST has phase loss
Check installation wiring
Check input voltage
Check the motor and cables
E.FO
Power Module 
Protection
1. The three output phases have phase - to-
phase short circuit or ground short circuit
Re-wiring, confirm whether the 
insulation of the motor is good
2. Instantaneous overcurrent of the inverter
See Overcurrent Countermeasures
3. The air duct is blocked or the fan is 
damaged
Unclog the duct or replace the fan
4. The ambient temperature is too high
reduce ambient temperature
5. The control board connection or plug-in 
    is loose
Check and reconnect
6. The current waveform is abnormal due to 
    the lack of output phase
Check wiring
7. The auxiliary power supply is damaged, 
    and the driving voltage is undervoltage
seek service
8. Inverter module bridge arm straight 
    through
seek service
9. The control panel is abnormal
seek service
E.OH1
radiator 
overheating
1. The ambient temperature is too high
reduce ambient temperature
2. Duct blockage
Clean up the air duct
3. The fan is broken
replace the fan
4. The inverter module is abnormal seek service
5. Temperature check circuit failure
seek service
E.OH2
rectifier bridge 
overheating
1. The ambient temperature is too high
reduce ambient temperature
2. Duct blockage
Clean up the air duct
3. The fan is broken
replace the fan
4. Temperature check circuit failure
seek service
E.OL2
Inverter overload
1. Motor parameters are inaccurate
Carry out motor parameter auto-
tuning again
2. Excessive load
Choose a higher power inverter
3. The amount of DC braking is too large
Reduce the DC braking current and 
prolong the braking time
4. Acceleration time is too short Extend acceleration time
5. Grid voltage is too low Check grid voltage
6. The V/F curve is not suitable
Correctly set the V/F curve and torque 
boost