NVF5 Series User Manual Appendix B Parameter list
Code
Name
Setting Range
Default
Change
Starting frequency
F1.07
DC braking
wait time
(0.0 ~ 100.0)s
0.0s
○
F1.08
DC braking
current
( 0.0 ~ 100.0 ) % ( Rated
Current)
0.0%
○
F1.09
DC braking time
(0.00 ~ 100.0)s
0.0s
○
F1.10
Forward/Reverse
Deadband Time
(0.0 ~ 300.0)s
0.0s
○
F1.11
Forward/Reverse
Switch Mode
0 :
Operating frequency lower
limit(F0.09) switching
1 :
Starting frequency(F1.01)
switching
0
○
F1.12
Accel. / Decel. Mode
Selection
0:Ramp Accel./Decel.
1:S curve Accel./Decel. 1
2:S curve Accel./Decel. 2
0
◎
F1.13
S-curve Scale of
Starting Time
(0.0 ~ 100.0)%
30.0%
◎
F1.14
S-curve Scale of
Stopping Time
(0.0 ~ 100.0)%
30.0%
◎
F2 Motor Parameter Group
F2.00 Motor Type
0:AC Induction Motor
1:Reserve
2:Reserve
0
◎
F2.01 Motor NP Power
(0.1 ~ 1000.0)kW
Depend on
motor type
◎
F2.02 Motor NP Voltage
0V ~ Inverter Rated Voltage
Depend on
motor type
◎
F2.03 Motor NP Current
(0.01~ 1000.00)A
Depend on
motor type
◎
F2.04 Motor NP Frequency
0.01Hz ~
Max. Output
Frequency F0.07
Depend on
motor type
◎
F2.05 Motor Poles
2 ~ 24
Depend on
motor type
◎
F2.06 Motor NP RPM
(0 ~ 60000)rpm
1430
◎
F2.07
Motor Stator
Impedance
(0.001 ~ 65.535)Ω(Inverter
Power <= 55kW)
(0.0001 ~ 6.5535)Ω(Inverter
Power > 55kW)
Depend on
motor type
◎
F2.08 Motor Rotor Resistor
(0.001 ~ 65.535)Ω(Inverter
Power <= 55kW)
(0.0001 ~ 6.5535)Ω(Inverter
Power > 55kW)
Depend on
motor type
◎
F2.09
Motor Leakage
Inductance
(0.01 ~ 655.35)mH(Inverter
Power <= 55kW)
Depend on
motor type
◎
- 115 -

Table of Contents