8 - FAULTS
When the PLC detects an issue, it triggers a fault.
8.1 - Fault type
Faults may either be "maintenance" or "danger" type faults.
"Maintenance" faults are information provided to the user and signal that the unit is not operating correctly, but that this does not
have any immediate consequences (a fouled lter, for example). These may be cleared once the issue has been resolved.
"Danger" faults are issues which prevent the unit from operating; the unit will shut down immediately (or after the fan delay). The
issue must be resolved before the unit can be restarted. The faults may be cleared once the unit has been shut down and the fault
has disappeared.
"Maintenance" faults may be congured as "danger" faults using parameters P602 to P651. Conversely, for safety reasons, it is 
not possible to congure "danger" faults as "maintenance" faults.
8.2 - Fault relays
The PLC contains a faults summary relay. This relay is a 250Vac / 6A type relay. It is triggered when at least one "maintenance"
or "danger" fault is present. If it is an EC motor warning from one of the fans, its triggering depends on parameter P292.
Its action direction is congurable (P882).
8.3 - Fault memory
The PLC stores the last 100 faults and the date and time that each of these faults occurred. This is menu
4 "fault memory". This memory cannot be cleared.
8.4 - List of faults
Here is the list of the di󰀨erent faults and warnings
No. Designation of faults
1 powering down
2 re protection
4 frost protection
11 Intake FMA1 EC motor
31 Exhaust FMA1 EC motor
21 Intake FMA1 EC motor warning
41 Exhaust FMA1 EC motor warning
48 Intake air ow low limit
49 Extraction air ow low limit
50 intake air ow rate
51 exhaust air ow rate
52 intake lter 1 clogged
53 intake lter 1 blocked
58 exhaust lter 1 clogged
59 exhaust lter 1 blocked
71 electric heater manual safety thermostat
73 DX unit
80 Duct pressure too low
81 Duct pressure too high
82 Supply air temperature too low
83 Supply air temperature too high
84 Return temperature too low
85 Return temperature too high
86 Room temperature too low
87 Room temperature too high
90 fresh air temperature sensor
91 supply air temperature sensor
92 return air temperature sensor
93 room temperature sensor
101 Loss of communication with the intake FMA1
121 Loss of communication with the extraction FMA1
140 Loss of communication with main box energy meter
150 Loss of communication with Th-Tune