EasyManua.ls Logo

CIAT FLOWAY ACCESS - 9.9 - Energy meter

CIAT FLOWAY ACCESS
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. Description
Setting
Unit
Access
level
Enumeration By default
Extraction FMA 1 information
2220 Calculated min. speed rpm 1
2221 Calculated max. speed rpm 1
2222 Speed requested rpm 1
2223 Current speed rpm 1
2224 Current consumed A 1
2225 Power input W 1
2226 Motor temperature °C 1
2227 Operating counter h 1
2230 Fault summary
0 : inactive
1 : active
1
2231 Communication state
0 : inactive
1 : active
1
2234 Warning summary
0 : inactive
1 : active
1
2235 Warning status 1
2238 Motor type 1
2239 Version number 1
9.9 - Energy meter
No. Description
Setting
Unit
Access
level
Enumeration By default
3000 Energy consumed 0 kWh 1
3001 Instantaneous power 0 W 1
3002 Voltage 0 V 1
3004 Voltage L1 - L2 0 V 1
3005 Voltage L3 - L2 0 V 1
3006 Voltage L1 - L3 0 V 1
3008 Current L1 0 A 1
3009 Current L2 0 A 1
3010 Current L3 0 A 1
3012 Fault summary
0 : Fault not present
1 : Fault present
1
3013 Communication state
0 : ofine
1 : online
1
3014 Serial number 1
3015 Version number 1
9 - PARAMETERS
EN-59 FLOWAY ACCESS

Related product manuals