Air handling units for
swimming pools
17
Junior BCP
- Align precisely both parts of the connection (unit and tubes). There
is no error risk when both tubes have different diameters.
- Run a pressure test in the cooling tubes and a search for leaks to
verify the cooling installation.
- Create a vacuum in the installation to eliminate humidity inside the
circuit.
- Charge the unit with gas as per the data stated in the technical
characteristic table. If the equivalent length
of the cooling lines is over 6 m, an additional
charge will be needed per meter as per the
following table.
Connection of the unit to the cooling lines
For the refrigerant lines, use only cooling type seamless tubes. Under
no circumstance use sanitary type cooper pipe.
Following these steps is recommended:
- Revise and clean the tube ends to eliminate the burs from cutting
them and any other impurity that could have deposited inside or on
the outer surface. How clean the tubes are will dictate the degree or
airtightness. Also, we will avoid the dirt formation that may collapse
some spots in the cooling circuit.
- Apply isolator to the tubes, covering them and affi x it with tape. The
material used must guarantee air tightness at operating pressure
and temperature.
- Remove the plugs that protect the cooling connections of the unit
precisely at the moment of connecting the tubes.
Note: Check the undercooling of the fl uid when fi lling out the "operation
verifi cation sheets" to make sure the charge is correct.
• Pressure drops in elbows expressed as equivalent lengths (m):
Maximum equivalent length
of the cooling line:
ASW = 40m
Maximum equivalent length
of the cooling line:
ASJ, ASN and ASM = 15m
BCP unit
BCP Unit
ASW
Air-cooled unit
ASJ, ASN and ASM
Air-cooled unit
ASW, ASN and ASM
Air-cooled unit
Maximum equivalent length
of the cooling line:
ASW, ASJ, ASN y ASM = 7m
Max. geometric height 30 m
Max. geometric height 15m
Max. height 6m
L liquid line
G gas line
Siphon in gas line every 3 meters of shoulder
G
GGLL
L
BCP unit
Tube diameter (inches) 5/8” 7/8” 1 1/8” 1 3/8” 1 5/8” 2 1/8”
Equivalent elbow length 45º (m)
0,30 0,39 0,48 0,60 0,75 0,90
Equivalent elbow length 90º (m)
0,54 0,72 0,90 1,10 1,30 1,65
Equivalent elbow length 180º (m)
0,80 1,00 1,30 1,80 2,00 2,60
Nominal diameter 1/4” 3/8” 1/2” 5/8” 3/4” 7/8” 1” 1 1/8” 1 3/8” 1 5/8”
Indoor section (cm
2
)
0,149 0,444 0,900 1,505 2,282 3,120 4,290 5,346 7,850 10,100
Liquid line charge (g/m)
18 53 107 180 272 376 512 638 937 1325
Gas line charge (g/m)
-- 0,19 0,38 0,64 0,97 1,33 1,83 2,30 3,30 4,00