Instruction Manual
53
Value Description
ID Charge Point identifier
Cache max. size
Maximum size of the
Authorization Cache,
that autonomously main-
tains a record of previously presented identifiers that have been suc-
cessfully authorized by the Central System.
It can be viewed accessing to the following URL:
http://<IP>:8080/services/cmd/dump_cache.xml
Use OCPP time
synchronization
YES: Synchronization of date and time -> Enabled.
NO: Synchronization of date and time -> Disabled.
NOTE: Date and Time is sent from backend on each heartbeat
response.
Energy for Start/
Stop transaction
PARTIAL: Consumed value of energy by the vehicle sent between
start and stop.
TOTAL: actual count of the total accumulated energy meter sent
between start and stop.
Energy for
MeterValues
PARTIAL: Sends partial energy consumption while vehicle is charg-
ing.
TOTAL: sends the actual count of the total accumulated energy
meter.
User confirmation
required on
remote start
ON: user confirmation needed to proceed with a remote start (i.e.
touch the screen)
OFF: user confirmation NOT needed to proceed with a remote start