EasyManua.ls Logo

Cisco NCS 5501 SE

Cisco NCS 5501 SE
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A dual pole breaker is needed for the installation. For NCS 5501 and 5501-SE, the rating of the dual pole
breaker is 40A with wire size of 10 AWG. For Cisco NCS 55A1-36H-S, NCS 5502 and 5502-SE, the
rating of the dual pole breaker is 80A with wire size of 6 AWG.
Note
Step 1
Verify that the correct fuse panel is installed in the top mounting space.
For a 40-72 VDC power supply for maximum 1100 W power, the fuse rating must be 80 A. There is an option for 240-380
VDC power supply for maximum 1100 W power, the fuse rating must not exceed 40 A.
Step 2
Measure and cut the cables as needed to reach the chassis from the fuse panel.
Step 3
Dress the power according to local practice.
Step 4
Connect the office battery and return cables according to the fuse panel engineering specifications.
Step 5
Insert the DC connector into the DC receptacle on the power supply.
Figure 18: Connecting DC Power
Step 6
Ensure that the locking mechanism has engaged.
Hardware Installation Guide for Cisco NCS 5500 Series Fixed-Port Routers
31
Install the Chassis
Connect DC Power to the Chassis

Table of Contents