1-32
Cisco ONS 15454 DWDM Procedure Guide, R8.0
78-17704-02
Chapter 1 Install the Shelf and Common Control Cards
NTP- G7 Install the Power and Ground
NTP-G7 Install the Power and Ground
Warning
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003
Warning
This equipment is intended to be grounded. Ensure that the host is connected to earth ground during
normal use.
Statement 39
Warning
Use copper conductors only.
Statement 1025
Purpose This procedure installs power feeds and grounds the ONS 15454.
Tools/Equipment ANSI and ETSI:
#2 Phillips Dynamometric screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Screws
Ground cable 13.3-mm² (#6 AWG) stranded
Listed pressure terminal connectors such as ring and fork types;
connectors must be suitable for #10 AWG copper conductors
Wire cutters
Wire strippers
Crimp tool
Fuse panel
ANSI only:
Power cable (from fuse and alarm panel to assembly), #10 AWG,
copper conductors, 194 degrees F [90 degrees C])
Wire wrapper
ETSI only:
Power cable (from fuse panel to MIC-A/P and to MIC-C/T/P), shipped
with the ONS 15454 ETSI
Two-hole grounding lug, shipped with the ONS 15454 ETSI
Prerequisite Procedures NTP-G4 Open and Remove the FMEC Cover (ETSI Only), page 1-25
NTP-G6 Install the MIC-A/P and MIC-T/C/P FMECs (ETSI Only), page
1-30
NTP-G5 Remove the Backplane Covers (ANSI Only), page 1-28
Required/As Needed Required
Onsite/Remote Onsite
Security Level None