BOILER BOOK CFC-E PRODUCT OFFERING
6
PRODUCT OFFERING
Dimensions, ratings, and product information may change to meet current market requirements and
product improvements. Therefore, use this information as a guide.
Standard Equipment
Equipment described below is for the standard boiler offering:
1. The Boiler
A. Each boiler size is designed for a Maximum Allowable Working Pressure (MAWP) of 125 psig
(8.6 Bar), constructed in accordance with the ASME Code Section IV and bear the “H” stamp.
B. The insulated pressure vessel is mounted on a base and a powder coated steel casing is
provided.
C. A drain valve connection is provided at the front bottom for field piping of a boiler drain valve,
which can be furnished as an option.
2. Boiler Trim and Controls
The following items are furnished:
Probe Type Low Water Cutoff control, manual reset.
High Water Temperature Cutoff, manual reset.
NTC (negative temp. coefficient) sensor for hot water supply temperature.
NTC sensor for hot water return temperature.
ASME Safety Relief Valve set @ 125 psig. (8.6 Bar) (Optional SRV set points available.)
Combination Temperature/Pressure Gauge.
3. Burner Control
A. The Falcon
controller is an integrated burner management and modulation control with a color
touch-screen display/operator interface. Its functions include the following:
Two (2) heating loops with PID load control.
Burner sequencing with safe start check, pre-purge, direct spark ignition, and post purge.
Electronic ignition.
Flame Supervision.
Safety shutdown with time-stamped display of lockout condition.
Variable speed control of the combustion fan.
Supervision of low and high gas pressure, air proving, stack back pressure, high limit, and low
water.
First-out annunciator.
Real-time data trending.
(3) pump/auxiliary relay outputs.
Modbus communication capability.
Outdoor temperature reset.
Remote firing rate or setpoint control
Setback/time-of-day setpoint
Lead/Lag for up to 8 boilers