Prometha™ Installation
750-441
14
10 - Tag Lists
Read-only tags for Prometha™ compatible devices
Hawk ICS
Point Name Data Type
1 Drive Fault BI
2 Modbus Com Error BI
3 Low Water BI
4 BC Alarm BI
5 Boiler Limits Open BI
6 High Stack Temp Alarm BI
7 High Stack Temp SD BI
8 External Interlock BI
9 I/O module fault BI
10 Steam Sensor Fail BI
11 Air Drive out of Position Alarm BI
12 Gas Drive out of Position Alarm BI
13 F/A Ratio Controller Fault BI
14 No Fuel Selected BI
15 Low Clogix Battery BI
16 Non Recycle Limit Relay Fail BI
17 Recyle Limit Relay Fail BI
18 Remote Modulation Signal Fail BI
19 Header Sensor Fail BI
20 TC Channel Fail BI
21 Low O2 Alarm BI
22 High Limit Alarm BI
23 ALWCO BI
24 Low Gas Pressure/Low Oil Temp BI
25 High Gas Pressure/High Oil Temp BI
26 Low Oil Pressure BI
27 High Oil Pressure BI
28 Oil Drawer Switch Not Made BI
29 Low Atomizing Air Pressure BI
30 Low Combustion Air Pressure BI
31 AUX Alarm 1 BI
32 AUX Alarm 2 BI
33 Blower On BI
34 Purge Input BI
35 Release To modulate Input BI
36 Low Fire Switch BI
37 High Fire Switch BI
38 Ready to start/Limits Closed BI
39 External Start Interlock BI
40 ALFCO BI
41 Pilot BI
42 Main Fuel Valve Open BI
43 Fuel 1 Selected BI
44 Fuel 2 Selected BI