Prometha™ Installation
750-441
27
Hawk 4000 V2
Point Name Data Type
1 Drive Fault BI
2 Modbus Comm Error BI
3 Lo Water BI
4 Burner Control Alm BI
5 Boiler Limits Open BI
6 Hi Stack Temp Alm BI
7 Hi Stack Temp Shutdown BI
8 External Interlock BI
9 I/O module fault BI
10 Steam Sensor Fail BI
11 Air Actuator Out Of Pos Alm BI
12 NG Actuator Out Of Pos Alm BI
13 F/A Ratio Controller Fault BI
14 No Fuel Selected BI
15 Low ControlLogix Battery BI
16 Non Recycle Limit Relay Fail BI
17 Recyle Limit Relay Fail BI
18 Rem Modulation Signal Fail BI
19 Header Pressure Sensor Fail BI
20 Temp Channel 0-5 Fail BI
21 Lo O2 Alm BI
22 Hi Limit Alm BI
23 ALWCO BI
24 Lo Gas Pressure/Lo Oil Temp BI
25 Hi Gas Pressure/Hi Oil Temp BI
26 Lo Oil Pressure BI
27 Hi Oil Pressure BI
28 Oil Drawer Switch Not Made BI
29 Lo Atomizing Air Pressure BI
30 Lo Combustion Air Pressure BI
31 Stack Damper High Pressure BI
32 AUX Alm 2 BI
33 Blower On BI
34 Purge Input BI
35 Release To Modulate Input BI
36 Lo Fire Switch BI
37 Hi Fire Switch BI
38 Ready to start/Limits Closed BI
39 External Start Interlock BI
40 ALFCO BI
41 Pilot BI
42 Main Fuel Valve Open BI
43 Fuel 1 Selected BI
44 Fuel 2 Selected BI
45 Heart Beat To BMS BI
46 LWCO Shutdown BI
47 Rem Enable Input BI
48 Burner Switch BI