Prometha™ Installation
750-441
19
100 Fuel3 Actuator Out Of Pos Alm BI
101 Fuel3 Actuator Feedback Fail Lo Alm BI
102 Fuel3 Actuator Feedback Fail Hi Alm BI
103 Stack Pressure Input Fail BI
104 Hi Stack Pressure Alm BI
105 Stack Damper Not Open Alm BI
106 O2 Calibration Failed BI
107 Lo Steam Pressure/Water Temp Alm BI
108 Processor Test Fail Alm BI
109 O2 Trim Internal Alm BI
110 Firetube or Flextube 1 = Flextube BI
111 Reserved for Cleaver Brooks BI
112 VSD Limits Internal Alm BI
113 Gas Actuator 2 Out Of Pos Alm BI
114 Gas Actuator 2 Feedback Fail Lo Alm BI
115 Gas Actuator 2 Feedback Fail Hi Alm BI
116 Actuator Modbus Communication Error BI
117 Air Actuator Modbus Comm Error Node 1 BI
118 Gas Actuator Modbus Comm Error Node 2 BI
119 Gas Act 2 Modbus Comm Error Node 3 BI
120 Oil Actuator Modbus Comm Error Node 5 BI
121 FGR Actuator Modbus Comm Error Node 7 BI
122 Reserved BI
123 Reserved BI
124 2nd Stg Outlet Wtr Temp Sensor Failed BI
125 Wtr Temp Second Stg Out Hi BI
126 Air Actuator Man Override Btn Press BI
127 Gas Actuator 1 Man Override Btn Press BI
128 Gas Actuator 2 Man Override Btn Press BI
129 Oil Actuator Man Override Btn Press BI
130 FGR Actuator Man Override Btn Press BI
131 Fuel 3 Act 1 Man Override Btn Press BI
132 Fuel 3 Act 2 Man Override Btn Press BI
133 Communication from BMS Failed BI
134 Combustion Air Pressure Hi BI
135 Wtr FLo Lo BI
136 Wtr Level Signal Failed BI
137 Remote Setpoint Signal Failed BI
138 Lo O2 Shutdown BI
139 Air Actuator Fault BI
140 Fuel 1 Actuator 1 Fault BI
141 Fuel 1 Actuator 2 Fault BI
142 Fuel 2 Actuator 1 Fault BI
143 Fuel 2 Actuator 2 Fault BI
144 FGR Actuator Fault BI
145 Fuel 2 Actuator 2 Pos Deviation BI
146 Fuel 2 Actuator 2 Feedback Lo BI
147 Fuel 2 Actuator 2 Feedback Hi BI
148 Fuel 2 Actuator 2 Man PB Press BI
149 VFD Feedback Lo BI
150 VFD Feedback Hi BI
Hawk 1000 (continued)