Tranquility
®
20
(TS) Series
Models TSD/H/V 006 - 070
60Hz - HFC-410A
INSTALLATION, OPERATION
& MAINTENANCE
97B0075N06
Revised: June 5, 2020
Table of Contents
Model Nomenclature - General Overview 3
General Information 4
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
Electrical - Line Voltage 20
Electrical - Power Wiring 26
Electrical - Power & Low Voltage Wiring 27
Electrical - Low Voltage Wiring 28
Electrical - Thermostat Wiring 29
TS Blower Performance Data - (ECM Motor) -
Standard Unit - No Reheat 30
TS Blower Performance Data - Standard Unit -
No Reheat (PSC Motor) 31
TS Blower Performance Data - Units with
ClimaDry
®
(PSC Motor) 32
ECM Blower Control 33
Typical Wiring Diagram - Units with CXM Board
and ECM Fan Motor (Single Phase) 35
Typical Wiring Diagram - Units with CXM Board
and PSC Fan Motor (Single Phase) 36
Typical Wiring Diagram - Units with DXM2 Board
and PSC Fan Motor (Three Phase) 37
Typical Wiring Diagram - Units with CXM Board,
ECM Fan Motor, and MPC (DDC) Controls
(Single Phase) 38
CXM Controls 39
DXM2 Controls 40
Safety Features - CXM and DXM2 Controls 45
ClimaDry
®
Modulating Reheat Option 47
Unit Starting and Operating Conditions 49
Piping System Cleaning and Flushing 50
Flushing/Purging Units with ClimaDry
®
51
Unit and System Checkout 52
Unit Start-Up Procedure 53
Unit Operating Conditions 55
Preventive Maintenance 60
Functional Troubleshooting 61
Performance Troubleshooting 62
Start-Up Log Sheet 63
Functional Troubleshooting 64

Questions and Answers

  • T
    Tanner RamseyAug 18, 2025
    How to troubleshoot main power problems in ClimateMaster Tranquility TSH 070 Heat Pump?
    • M
      Martin MorseAug 18, 2025
      If the green status LED is off on your ClimateMaster Heat Pump, check the line voltage circuit breaker and disconnect. Also, check for line voltage between L1 and L2 on the contactor, 24VAC between R and C on CXM/DXM2, and the primary/secondary voltage on the transformer.
  • W
    williamellisonAug 20, 2025
    How do I troubleshoot Condensate Fault Code 6 on my ClimateMaster Tranquility TSH 070?
    • J
      jessicastricklandAug 21, 2025
      If your ClimateMaster Heat Pump shows Condensate Fault Code 6, check for blockage and clean the drain. Inspect the trap dimensions and ensure its location is ahead of the vent. Verify the piping slope is away from the unit and check the slope of the unit toward the outlet. Ensure proper venting by checking the vent location. Also, check for moisture shorting to the air coil and replace the air filter. If there is restricted return air flow, find and eliminate the restriction, and increase the return duct and/or grille size.
  • K
    Kiara MillerAug 23, 2025
    What to do if my ClimateMaster Tranquility TSH 070 shows HP Fault Code 2 High Pressure?
    • L
      Linda MillerAug 23, 2025
      If your ClimateMaster Heat Pump displays a High Pressure fault (Code 2), the issue might stem from several causes. If cooling, check the pump or valve operation/setting and ensure proper water flow. Make sure the water temperature is within the specified range for cooling. If heating, inspect the air filter and clean or replace if dirty. Also, examine the fan motor operation for any airflow restrictions. Ensure the air coil is clean and that the external static pressure aligns with the blower table. Verify that the return air temperature is within the design parameters, and check superheat/subcooling against the typical operating condition table. Finally, check the switch continuity and operation, replacing if necessary.
  • R
    Richard ScottAug 26, 2025
    What causes LP/LOC Fault Code 3 Low Pressure / Loss of Charge in ClimateMaster Tranquility TSH 070?
    • F
      fmurphyAug 26, 2025
      If your ClimateMaster Heat Pump shows a Low Pressure/Loss of Charge fault (Code 3), it may be due to insufficient charge. Check for refrigerant leaks. Also, check the charge and start-up water flow.
  • J
    joditurnerAug 27, 2025
    What does Over/Under Voltage Code 7 mean on my ClimateMaster Tranquility TSH 070?
    • J
      John ChungAug 28, 2025
      If your ClimateMaster Heat Pump displays an Over/Under Voltage fault (Code 7), check the power supply and 24VAC voltage, both before and during operation. Inspect the power supply wire size. Consider whether a hard start kit is needed for the compressor. Also, check the 24VAC and unit transformer tap for correct power supply voltage. This applies to both undervoltage and overvoltage scenarios.
  • B
    Brian HarrisAug 30, 2025
    How to fix LT1 Fault Code 4 Water coil low temperature limit in ClimateMaster Tranquility TSH 070?
    • M
      Madeline LeeAug 30, 2025
      If your ClimateMaster Heat Pump displays a Water coil low temperature limit fault (LT1 Fault Code 4), it could be due to several reasons. If heating, check the pump operation or water valve operation/setting for reduced or no water flow. Ensure that the strainer or filter is not plugged, clean or replace if necessary. Also, check and adjust the water flow to the proper rate. If using antifreeze, check the antifreeze density with a hydrometer. If needed, clip the JW3 jumper for antifreeze (10°F [-12°C]) use. Ensure the water temperature is within the design parameters and check the temperature and impedance correlation per the chart.
  • D
    Debra NortonSep 1, 2025
    What causes LT2 Fault Code 5 Air coil low temperature limit in ClimateMaster Tranquility TSH 070?
    • C
      Charles OrrSep 1, 2025
      If your ClimateMaster Heat Pump displays an Air coil low temperature limit fault (LT2 Fault Code 5), check for a dirty air filter and clean or replace it if necessary. Verify the fan motor operation and airflow isn't restricted. Also, check the external static pressure against the blower table. If the air temperature is out of range, ensure that the entering air temperature is within design parameters. If the temperature limit setting is improper (30°F vs 10°F [-1°C vs -12°C]), note that normal airside applications will require 30°F [-1°C] only. Finally, check the temperature and impedance correlation per the chart.
  • I
    Isaiah CummingsSep 3, 2025
    Why does my ClimateMaster Tranquility TSH 070 unit short cycle?
    • S
      Scott EvansSep 3, 2025
      If your ClimateMaster Heat Pump is short cycling, start by checking and cleaning the air filter. Also, ensure the unit isn't in 'test mode'; if it is, reset the power or wait 20 minutes for it to automatically exit. Check the sizing for the actual load of the space. Finally, check the compressor overload and replace if necessary.
  • S
    Sarah SolisSep 5, 2025
    Why does only the fan run on my ClimateMaster Tranquility TSH 070 Heat Pump?
    • C
      Cynthia GutierrezSep 6, 2025
      If only the fan is running on your ClimateMaster Heat Pump, first ensure the thermostat is set for heating or cooling operation. Check for any lockout codes and reset the power. Inspect the compressor overload and replace if necessary. Finally, check the thermostat wiring at the heat pump, jumpering Y and R for compressor operation in test mode.
  • L
    Lisa WareSep 8, 2025
    What does Unit Performance Sentinel Code 8 mean for ClimateMaster Heat Pump?
    • E
      Erica ColeSep 8, 2025
      If your ClimateMaster Heat Pump displays Unit Performance Sentinel Code 8, it could indicate a few issues. If in heating mode and LT2 is greater than 125°F [52°C], check for poor air flow or an overcharged unit. If in cooling mode and LT1 is greater than 125°F [52°C] or LT2 is less than 40ºF [4ºC], check for poor water flow or air flow.

Summary

Model Nomenclature and Overview

Model Type Identification

Explains the coding for unit identification.

Unit Size Codes

Details the size codes for different models.

General Information and Safety

Safety Warnings and Precautions

Covers DANGER, WARNING, CAUTION, and NOTICE classifications.

Horizontal Unit Installation

Mounting and Suspension

Explains how to hang and suspend horizontal units.

Condensate Piping Installation

Details requirements for condensate drain line installation.

Duct System Design Considerations

Outlines duct system design considerations for optimal performance.

Vertical Unit Installation

Mounting Procedures

Covers guidelines for mounting vertical units.

Ground-Loop Heat Pump Applications

Ground-Water Heat Pump Applications

Electrical - Line Voltage

Electrical - Power Wiring

Electrical - Power & Low Voltage Wiring

Electrical - Low Voltage Wiring

Electrical - Thermostat Wiring

ECM Blower Control

CXM Controls Overview

DXM2 Controls Overview

Field Selectable Test Mode

Explains test mode for checking control operation.

Field Configuration Options

Details jumper and DIP switch settings for unit configuration.

DXM2 DIP Package #1 (S1) Settings

Covers settings for UPS, compressor staging, and thermostat type.

DXM2 DIP Package #2 (S2) Settings

Details accessory relay options and dehumidification modes.

Safety Features for Controls

Compressor Protection Features

Explains anti-short cycle, fault retry, and lockout mechanisms.

Unit Performance Sentinel (UPS)

Details the UPS feature indicating inefficient operation.

ClimaDry Modulating Reheat

Unit and System Checkout

Unit Start-up Procedure

Step-by-Step Start-up Guide

Provides step-by-step instructions for unit start-up.

Preventive Maintenance Schedule

Functional Troubleshooting Guide

Power and Pressure Faults

Lists causes and solutions for power and pressure issues.

Temperature Limit Faults

Covers low water and air temperature limit faults.

Performance Troubleshooting Guide

Capacity and Pressure Issues

Troubleshoots insufficient capacity and high/low pressure problems.

ClimateMaster Tranquility TSH 070 Specifications

General IconGeneral
BrandClimateMaster
ModelTranquility TSH 070
CategoryHeat Pump
LanguageEnglish