Tranquility
®
20
(TS) Series
Models TSD/H/V 006 - 070
60Hz - HFC-410A
INSTALLATION, OPERATION
& MAINTENANCE
97B0075N06
Revised: June 5, 2020
Table of Contents
Model Nomenclature - General Overview 3
General Information 4
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
Electrical - Line Voltage 20
Electrical - Power Wiring 26
Electrical - Power & Low Voltage Wiring 27
Electrical - Low Voltage Wiring 28
Electrical - Thermostat Wiring 29
TS Blower Performance Data - (ECM Motor) -
Standard Unit - No Reheat 30
TS Blower Performance Data - Standard Unit -
No Reheat (PSC Motor) 31
TS Blower Performance Data - Units with
ClimaDry
®
(PSC Motor) 32
ECM Blower Control 33
Typical Wiring Diagram - Units with CXM Board
and ECM Fan Motor (Single Phase) 35
Typical Wiring Diagram - Units with CXM Board
and PSC Fan Motor (Single Phase) 36
Typical Wiring Diagram - Units with DXM2 Board
and PSC Fan Motor (Three Phase) 37
Typical Wiring Diagram - Units with CXM Board,
ECM Fan Motor, and MPC (DDC) Controls
(Single Phase) 38
CXM Controls 39
DXM2 Controls 40
Safety Features - CXM and DXM2 Controls 45
ClimaDry
®
Modulating Reheat Option 47
Unit Starting and Operating Conditions 49
Piping System Cleaning and Flushing 50
Flushing/Purging Units with ClimaDry
®
51
Unit and System Checkout 52
Unit Start-Up Procedure 53
Unit Operating Conditions 55
Preventive Maintenance 60
Functional Troubleshooting 61
Performance Troubleshooting 62
Start-Up Log Sheet 63
Functional Troubleshooting 64

Questions and Answers

  • L
    Lee LewisAug 18, 2025
    How to troubleshoot main power problems in ClimateMaster Heat Pump?
    • G
      Glen NixonAug 18, 2025
      If the green status LED is off on your ClimateMaster Heat Pump, check the line voltage circuit breaker and disconnect. Also, check for line voltage between L1 and L2 on the contactor, 24VAC between R and C on CXM/DXM2, and the primary/secondary voltage on the transformer.
  • J
    James HansenAug 20, 2025
    How do I troubleshoot Condensate Fault Code 6 on my ClimateMaster Tranquility TSV 009 Heat Pump?
    • J
      James Cole MDAug 20, 2025
      If your ClimateMaster Heat Pump shows Condensate Fault Code 6, check for blockage and clean the drain. Inspect the trap dimensions and ensure its location is ahead of the vent. Verify the piping slope is away from the unit and check the slope of the unit toward the outlet. Ensure proper venting by checking the vent location. Also, check for moisture shorting to the air coil and replace the air filter. If there is restricted return air flow, find and eliminate the restriction, and increase the return duct and/or grille size.
  • T
    Taylor SpencerAug 23, 2025
    What to do if my ClimateMaster Tranquility TSV 009 Heat Pump shows HP Fault Code 2 High Pressure?
    • D
      David McleanAug 23, 2025
      If your ClimateMaster Heat Pump displays a High Pressure fault (Code 2), the issue might stem from several causes. If cooling, check the pump or valve operation/setting and ensure proper water flow. Make sure the water temperature is within the specified range for cooling. If heating, inspect the air filter and clean or replace if dirty. Also, examine the fan motor operation for any airflow restrictions. Ensure the air coil is clean and that the external static pressure aligns with the blower table. Verify that the return air temperature is within the design parameters, and check superheat/subcooling against the typical operating condition table. Finally, check the switch continuity and operation, replacing if necessary.
  • J
    Justin WareAug 26, 2025
    What causes LP/LOC Fault Code 3 Low Pressure / Loss of Charge in ClimateMaster Tranquility TSV 009?
    • J
      Jasmine JonesAug 26, 2025
      If your ClimateMaster Heat Pump shows a Low Pressure/Loss of Charge fault (Code 3), it may be due to insufficient charge. Check for refrigerant leaks. Also, check the charge and start-up water flow.
  • S
    Sherry PrattAug 27, 2025
    What does Over/Under Voltage Code 7 mean on my ClimateMaster Heat Pump?
    • A
      April RomanAug 27, 2025
      If your ClimateMaster Heat Pump displays an Over/Under Voltage fault (Code 7), check the power supply and 24VAC voltage, both before and during operation. Inspect the power supply wire size. Consider whether a hard start kit is needed for the compressor. Also, check the 24VAC and unit transformer tap for correct power supply voltage. This applies to both undervoltage and overvoltage scenarios.
  • E
    Erika ReedAug 30, 2025
    How to fix LT1 Fault Code 4 Water coil low temperature limit in ClimateMaster Heat Pump?
    • B
      Beth MillerAug 30, 2025
      If your ClimateMaster Heat Pump displays a Water coil low temperature limit fault (LT1 Fault Code 4), it could be due to several reasons. If heating, check the pump operation or water valve operation/setting for reduced or no water flow. Ensure that the strainer or filter is not plugged, clean or replace if necessary. Also, check and adjust the water flow to the proper rate. If using antifreeze, check the antifreeze density with a hydrometer. If needed, clip the JW3 jumper for antifreeze (10°F [-12°C]) use. Ensure the water temperature is within the design parameters and check the temperature and impedance correlation per the chart.
  • Y
    yorkhannahSep 1, 2025
    What causes LT2 Fault Code 5 Air coil low temperature limit in ClimateMaster Tranquility TSV 009 Heat Pump?
    • D
      David FlynnSep 1, 2025
      If your ClimateMaster Heat Pump displays an Air coil low temperature limit fault (LT2 Fault Code 5), check for a dirty air filter and clean or replace it if necessary. Verify the fan motor operation and airflow isn't restricted. Also, check the external static pressure against the blower table. If the air temperature is out of range, ensure that the entering air temperature is within design parameters. If the temperature limit setting is improper (30°F vs 10°F [-1°C vs -12°C]), note that normal airside applications will require 30°F [-1°C] only. Finally, check the temperature and impedance correlation per the chart.
  • S
    Savannah SerranoSep 3, 2025
    Why does my ClimateMaster Tranquility TSV 009 unit short cycle?
    • T
      Tim RodriguezSep 3, 2025
      If your ClimateMaster Heat Pump is short cycling, start by checking and cleaning the air filter. Also, ensure the unit isn't in 'test mode'; if it is, reset the power or wait 20 minutes for it to automatically exit. Check the sizing for the actual load of the space. Finally, check the compressor overload and replace if necessary.
  • T
    Thomas NelsonSep 5, 2025
    Why does only the fan run on my ClimateMaster Tranquility TSV 009?
    • J
      Jeffrey WilsonSep 5, 2025
      If only the fan is running on your ClimateMaster Heat Pump, first ensure the thermostat is set for heating or cooling operation. Check for any lockout codes and reset the power. Inspect the compressor overload and replace if necessary. Finally, check the thermostat wiring at the heat pump, jumpering Y and R for compressor operation in test mode.
  • B
    brandonruizSep 8, 2025
    What does Unit Performance Sentinel Code 8 mean for ClimateMaster Heat Pump?
    • A
      Andrew GarrettSep 8, 2025
      If your ClimateMaster Heat Pump displays Unit Performance Sentinel Code 8, it could indicate a few issues. If in heating mode and LT2 is greater than 125°F [52°C], check for poor air flow or an overcharged unit. If in cooling mode and LT1 is greater than 125°F [52°C] or LT2 is less than 40ºF [4ºC], check for poor water flow or air flow.

Summary

Model Nomenclature and Overview

Model Type

Defines the unit model designation and series type.

Unit Size

Specifies the cooling/heating capacity range for the unit models.

Voltage

Lists available voltage configurations for the unit.

General Information and Safety

Safety Warnings and Precautions

Crucial safety instructions including DANGER, WARNING, CAUTION, and NOTICE.

Pre-Installation Procedures

Guidelines for unit preparation and site selection before installation.

Horizontal Installation

Mounting Horizontal Units

Instructions for suspending units using hanger brackets and threaded rods.

Vertical Installation

Piping Installation

Installation of Supply and Return Piping

Detailed guidelines for connecting water supply and return piping.

Ground-Loop Heat Pump Applications

Antifreeze

Requirements and calculations for using antifreeze in ground loops.

Ground-Water Heat Pump Applications

Water Quality Standards

Guidelines for evaluating water quality for heat exchanger compatibility.

Water Quality Standards

Electrical - Line Voltage

Electrical - Line Voltage

Compliance with electrical codes for field-installed wiring.

Electrical - Power Wiring

Power Connection

Guidelines for making line voltage connections to the unit.

Electrical - Power & Low Voltage Wiring

Thermostat Connections

Wiring procedures for connecting thermostats to control boards.

Low Water Temperature Cutout Selection

Field selection of temperature limits for water coil protection.

Electrical -Thermostat Wiring

Thermostat Installation

Best practices for thermostat placement and wiring connections.

ECM Blower Control

Dehumidification Mode Settings

Options for enabling and configuring dehumidification modes.

CXM Controls

DXM2 Controls

Field Selectable Inputs

Utilizing test mode for system diagnostics and fault code retrieval.

Field Configuration Options

Adjusting unit parameters using jumpers for specific configurations.

DIP Switches

Configuring DXM2 operation via various DIP switch settings.

DXM2 Control Start-up Operation

Procedure for initial unit startup and compressor delay sequences.

Safety Features - CXM and DXM2 Controls

Low Pressure Switch

How the low pressure switch detects and reacts to abnormal conditions.

Water Coil Low Temperature (LT1)

Protection against low water temperatures affecting the refrigerant circuit.

Air Coil Low Temperature (LT2)

Protection against low air temperatures impacting unit performance.

ClimaDry Modulating Reheat Option

ClimaDry Sequence Of Operation

How the ClimaDry® system functions in cooling, reheat, and heating modes.

Unit Starting and Operating Conditions

Piping System Cleaning and Flushing

Unit and System Checkout

Unit Checkout

Pre-power checks for unit components and wiring.

System Checkout

Verifying system water conditions, controls, and overall operation.

Unit Start-up Procedure

Unit Operating Conditions

Preventive Maintenance

Functional Troubleshooting

Low Pressure; Loss of Charge

Diagnosing issues related to low refrigerant charge or pressure.

Performance Troubleshooting

Insufficient Capacity

Identifying causes for reduced cooling or heating capacity.

Start-Up Log Sheet

Warranty (U.S. & Canada)

Warranty (International)

Grant of Limited Express Warranty

Details of the warranty coverage for CM products internationally.

ClimateMaster Tranquility TSV 009 Specifications

General IconGeneral
TypeWater Source Heat Pump
Cooling Capacity9, 000 BTU/h
RefrigerantR-410A
Phase1
Liquid Line Size3/8 in
Suction Line Size5/8 in

Related product manuals