EasyManua.ls Logo

ClimateMaster Tranquility TSV 009 - ECM Blower Control; Dehumidification Mode Settings

ClimateMaster Tranquility TSV 009
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
climatemaster.com
33
Tranquility
®
20 (TE) Series
Rev.: June 5, 2020
THE SMART SOLUTION FOR ENERGY EFFICIENCY
ECM Blower Control
The ECM fan is controlled by an interface board that
converts thermostat inputs and eld selectable CFM
settings to signals used by the ECM motor controller. Fan
speeds are selected with DIP switch settings. To take
full advantage of the ECM motor features, a multi-stage
thermostat should be used (2-stage heat/2-stage cool or
3-stage heat/2-stage cool).
Note: Power must be off to the unit for at least three
seconds before the ECM motor will recognize a speed
change. The motor will recognize a change in the CFM
Adjust or dehumidication mode settings while the
unit is powered.
There are four different airow settings from lowest
airow rate (speed tap 1) to the highest airow rate
(speed tap 4).
The charts below indicate settings for of the ECM
interface board, followed by detailed information for each
setting.
Cooling Settings: The cooling setting determines the
cooling (normal) CFM for all units with ECM motor.
Cooling (normal) setting is used when the unit is not in
dehumidication mode. Tap 1 is the lowest CFM setting,
while tap 4 is the highest CFM setting. To avoid air coil
freeze-up, tap 1 may not be used if the dehumidication
mode is selected. Consult submittal data or specications
catalog for the specic unit series and model to correlate
speed tap setting to airow in CFM.
Heating Settings: The heating setting determines the
heating CFM. Tap 1 is the lowest CFM setting, while
tap 4 is the highest CFM setting. Consult submittal data
or specications catalog for the specic unit series and
model to correlate speed tap setting to airow in CFM.
CFM Adjust Settings: The CFM adjust setting allows
four selections. The NORM setting is the factory default
position. The + or – settings adjust the airow by +/-
5%. The +/- settings are used to “ne tune” airow
adjustments. The TEST setting runs the ECM motor at
400 CFM/ton, example 2-ton = 800 CFM.
Dehumidication Mode Settings: The dehumidication
mode setting provides eld selection of humidity control.
When operating in the normal mode, the cooling airow
settings are determined by the cooling tap setting above.
When dehumidication is enabled there is a reduction
in airow in cooling to increase the moisture removal of
the heat pump. Consult submittal data or specications
catalog for the specic unit series and model to correlate
speed tap to airow in CFM. The dehumidication mode
can be enabled in two ways.
1. Constant Dehumidication Mode: When the
dehumidication mode is selected (via DIP switch or
jumper setting), the ECM motor will operatewith a
multiplier applied to the cooling CFM settings (approx.
20-25% lower airow). Any time the unit is running in
the cooling mode, it will operate at the lower airow
to improve latent capacity. The “DEHUM” LED will be
illuminated at all times. Heating airow is not affected
Note: Do not select dehumidication mode if cooling
setting is tap 1.
2. Automatic (Humidistat-controlled)
Dehumidication Mode: When the dehumidication
mode is selected (via DIP switch) AND a humidistat
is connected to terminal DH), the cooling airow
will only be reduced when the humidistat senses
that additional dehumidication is required. The DH
terminal is reverse logic. Therefore, a humidistat (not
dehumidistat) is required. The “DEHUM” LED will
be illuminated only when the humidistat is calling
for dehumidication mode. Heating airow is not
affected. Note: Do not select dehumidication mode
if cooling setting is tap 1.

Related product manuals