3.3 Installation of the CCM control unit
Start with the installation of the CCM control unit by looking at the wiring diagram included in the
delivery.
1. The CCM control unit and possible slave units should be mounted on a wall in a visible place
which can be easily accessed.
2. Mount the safety switch included in delivery on a wall near the CCM control unit, where the
switch can be easily accessed.
3.4 Electrical wiring
3.4.1 Electrical wiring of the CCM control unit
1. Lead the voltage supply to the safety switch.
2. From the safety switch lead the voltage supply to the CCM control unit and to possible slave
units.
3. Connect the conductors coming out from the CCM control unit to the UV lamp. following the
wiring diagram provided at the end of these instructions.
4. Connect the conductors of the SlideSafe safety lock of the hoods to the CCM control unit or a
slave unit.
3.4.2 Connecting the CCM control unit with the automation system of the building
The CCM control unit gives the possibility to send operational information to the automation sys-
tem of the real estate, and to request starting permission, if necessary. Detailed information is
provided in the wiring diagram at the end of these instructions.
Output:
Operating status
The system functions normally. A green light is lit in the control panel.
Common alarm
Alarm, the system has switch o. A red light is lit in the control panel.
Warning
Warning, action by the user is required. The system still functions.
A yellow light is lit in the control panel.
Input:
External control
The building automation has not given the permission for operation.
A red light is lit in the control panel.

Other manuals for Climecon CLEANMASTER Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Climecon CLEANMASTER Series and is the answer not in the manual?

Climecon CLEANMASTER Series Specifications

General IconGeneral
BrandClimecon
ModelCLEANMASTER Series
CategoryVentilation Hood
LanguageEnglish