Refrigerant piping
First connection method
1
2
3
5
4
a
A
L
1
L
2
L
3
L
4
L
5
C
D
E
b c d e f
B
C
D
E
Fig. 32
Ref. Pipe length Value
1
Maximum dierence in height
between outdoor units (located at
the top) and indoor units
30m
Maximum dierence in height
between outdoor units (located at
the bottom) and indoor units
20m
2
Pipes between the furthest indoor
unit and the first indoor branch
20m
3
Maximum equivalent length of the
pipe between the outdoor unit and
the furthest indoor unit
50m/70m (*)
4
Maximum dierence in height
between indoor units
8m
5
Equivalent pipe length from the
first branch to the nearest indoor
unit
15m
(*) 50 m (8-10.5 kW) - 70 m (12-14 + 16-18 kW)
Ref. Description
L Main pipe
L.... L Internal main pipes
a .... f Internal auxiliary pipes