EasyManua.ls Logo

CLIVET MSAN-XMI 200T - Wiring Method

CLIVET MSAN-XMI 200T
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
Electrical connections
The control line between the outdoor unit and
the indoor unit is BUS type. The addresses are
configured on site during installation.
w
a
CAUTION
Earth only at one point in the system since
multiple points can generate transmission
noise.
m
CAUTION
Within a group, connect only indoor units of
the same type (wall, ducted, recessed).
Connect the various indoor and outdoor units as shown
in the diagram below.
Fig. 55
1
Bus between outdoor unit and indoor units
Close the chain between P and Q in the last indoor unit
with the 120Ω resistor supplied with the outdoor unit.
Do not return the bus to the outdoor unit.
5.4 Wiring method
Communication with indoor unit: The communication line
P, Q, E must be connected in a chain leading from the
outdoor unit to each indoor unit and up to the last indoor
unit, connecting a 120Ω heater between terminals P and
Q. The correct and incorrect methods of connection are
shown below:
1
P Q E
P Q E P Q E P Q E P Q E
2 2 2 2
Fig. 56
1
Outdoor unit
2
Indoor unit
1
P Q E P Q E P Q E
P Q E
P Q E
2 2 2 2 2
Fig. 57
1
Outdoor unit
2
Indoor unit
Do not connect two chains from a single outdoor unit.
1
P Q E
P Q E
P Q E
P Q E
P Q E
2 2
22
Fig. 58
1
Outdoor unit
2
Indoor unit
After the last indoor unit, the communication cables must
not be led back to the outdoor unit as to do so would
form a closed circuit.
l
WARNING
The cross-section of each core of the
communication cabling must not be less than
0.75 mm
2
and the length must not exceed
1200 m. A communication error can occur
when the communication cabling exceeds
these limitations.
N1
1
N
2 N10
P Q E
P Q E
P Q E
P Q E P Q E P Q E

Related product manuals