TROUBLESHOOTING
H1
Description
Communication error between main control board and inverter module.
The unit shuts down.
The error code is displayed on the main PCB and user interface.
Possible causes
Abnormal power supply.
Transformer malfunction
Interference from a source of electromagnetic radiation.
Main PCB or inverter driven module damaged.
Procedure
H1
Main PCB or transformer power supply is abnormal
YES
Provide normal power supply
NO
Transformer malfunction
YES
Replace the transformer
NO
There is a source of electromagnetic radiation
near the unit, such as high-frequency transmitter or
other high-strength radiation device
YES
Remove the source of interference
NO
Replace the main PCB and the inverter driven
module