Addresses 0 - 15 are the addresses of the selected units.
(addresses)*100+240—(addresses)*100+299 , are read only.
Units in modular configuration
Reading logbook
Address function notes
240+(Address)*100
Operating mode
1 shutdown
2 cooling
3 not used
241+(Address)*100
SILENT mode
1 Standard
2 Silent
3 Super silent
242+(Address)*100 not used
243+(Address)*100 not used
244+(Address)*100
Twi unit inlet water temperature 1
245+(Address)*100
Two unit outlet water temperature 1
246+(Address)*100
Tw total outlet water temperature 1°C ; only for the master (0)
Address function notes
101 Double setpoint Enable/Disable 1/0
102 1st setpoint in cooling 5~20°C
103 2nd setpoint in cooling 5~20°C
104 not used
105 not used
106 temperature compensation in cooling Enable/Disable
107 point 1 temperature compensation in cooling 25~30°C
108 point 2 temperature compensation in cooling 35~40°C
109 temperature compensation value in cooling 0~15°C
110 not used
111 not used
112 not used
113 not used
Reading and writing register; 100 - 109 read only, 110 reading and writing.