Address function notes
247+(Address)*100
Outside temperature
1°C
248+(Address)*100
Compressor speed 1Hz
249+(Address)*100
Compressor input 1A
250+(Address)*100
Fan 1 Speed Current speed
251+(Address)*100
Fan 2 Speed Current speed
252+(Address)*100
Fan 3 Speed Current speed
253+(Address)*100
EXVA Current position
254+(Address)*100
EXVB Current position
255+(Address)*100
EXVC Current position
256+(Address)*100
SV4 0 Off, 1 On
257+(Address)*100
SV5 0 Off, 1 On
258+(Address)*100
SV8A 0 Off, 1 On
259+(Address)*100
SV8B 0 Off, 1 On
260+(Address)*100
4-way valve 0 Off, 1 On
261+(Address)*100
circulation pump 0 Off, 1 On
262+(Address)*100
SV1 0 Off, 1 On
263+(Address)*100
SV2 0 Off, 1 On
264+(Address)*100
HEAT1 0 Off, 1 On
265+(Address)*100
HEAT2 0 Off, 1 On
266+(Address)*100
Discharge temperature
1°C
267+(Address)*100
Suction temperature
1°C
268+(Address)*100
temperature T3A
1°C
269+(Address)*100
temperature Tz
1°C
270+(Address)*100
temperature T5
1°C
271+(Address)*100
P PRESSURE 10 kPa
272+(Address)*100
error / protection see error codes table
273+(Address)*100
last error / protection see error codes table
274+(Address)*100
software version HMI
275+(Address)*100
Discharge temperature 2
1°C
276+(Address)*100
temperature T3B
1°C
277+(Address)*100
temperature T6A
1°C