9. Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks
and component inspection procedures If afault exists that could compromise safety,
then no electrical supply shall be connected to thecircuit until it is satisfactorily dealt with.
If thefault cannot be corrected immediately but it is necessary to continue operation,
anadequate temporary solution shall be used. This shall be reported to theowner of
theequipment so all parties are advised. Initial safety checks shall include:
• that capacitors are discharged: this shall be done in asafe manner to avoid
possibility of sparking;
• that there no live electrical components and wiring are exposed while charging,
recoveringor purging thesystem;
• that there is continuity of earth bonding.
10. Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected from
theequipment being worked upon prior to any removal of sealed covers, etc. If it is
absolutely necessary to have anelectrical supply to equipment during servicing, then
apermanently operating form of leak detection shali be located at themost critical
point to warn of apotentially hazardous situation.
Particular attention shall be paid to thefollowing to ensure that by working on electrical
components, thecasing is not altered in such away that thelevel of protection is
affected. This shall include damage to cables, excessive number of connections,
terminals not made to original specification, damage to seals, incorrect fitting of
glands, etc.
• Ensure that apparatus is mounted securely.
• Ensure that seals or sealing materials have not degraded such that they no
longer serve thepurpose of preventing theingress of flammable atmospheres.
Replacement parts shall be in accordance with themanufacturer’s specifications.
Note: Theuse of silicon sealant may inhibit theeffectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated prior to
working on them.
11. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to thecircuit without
ensuring that this will not exceed thepermissible voltage and current permitted for
theequipment in use.Intrinsically safe components are theonly types that can be
worked on while live in thepresence of aflammable atmosphere. Thetest apparatus
shall be at thecorrect rating. Replace components only with parts specified by
themanufacturer. Other parts may result in theignition of refrigerant in theatmosphere
from aleak.