7
ENGLISH
12. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration,
sharp edges or any other adverse environmental effects. Thecheck shall also take into
account theeffects of aging or continual vibration from sources such as compressors
or fans.
13. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in thesearching for
or detection of refrigerant leaks. Ahalide torch (or any other detector using anaked flame)
shall not be used.
14. Leak detection methods
Thefollowing leak detection methods are deemed acceptable for systems containing
flammable refrigerants. Electronic leak detectors shall be used to detect flammable
refrigerants, but thesensitivity may not be adequate, or may need re-calibration.
(Detection equipment shall be calibrated in arefrigerant-free area.) Ensure that thedetector
is not apotential source of ignition and is suitable for therefrigerant used. Leak detection
equipment shall be set at apercentage of theLFL of therefrigerant and shall be calibrated
to therefrigerant employed and theappropriate percentage of gas (25 % maximum)
is confirmed.
Leak detection fluids are suitable for use with most refrigerants but theuse of
detergents containing chlorine shall be avoided as thechlorine may react with
therefrigerant and corrode thecopper pipe-work.
If aleak is suspected, all naked flames shall be removed/extinguished. If aleakage of
refrigerant is found which requires brazing, all of therefrigerant shall be recovered from
thesystem, or isolated (by means of shut off valves) in apart of thesystem remote
from theleak. Oxygen free nitrogen (OFN) shall then be purged through thesystem
both before and during thebrazing process.
15. Removal and evacuation
When breaking into therefrigerant circuit to make repairs - or for any other purpose
- conventional procedures shall be used. However, it is important that best practice
is followed since flammability is aconsideration. Thefollowing procedure shall be
adhered to:
• remove refrigerant;
• purge thecircuit with inert gas;
• evacuate;
• purge again with inert gas;
• open thecircuit by cutting or brazing.