CALOR 40 Manual Page 20 (total 27) COMAC CAL s.r.o.
Vin1 [pulse/l]
Ethylene glycol mixture ratio [%]
Q/P
4mA
[l/h, kW]
Q/P
20mA
[l/h, kW]
Baud rate
Meter's address
Energy - time tariff1
Energy - time tariff2
Energy - time tariff3
Reinitialization
The reinitialization option is suitable for industrial environments with frequent
occurrence of interfering electrostatic voltages and electromagnetic fields. When this option is
checked, the meter reloads system constants of the entire meter once a day.
Setting procedure:
1) Remove the top cover.
2) Connect the USB cable with PC with the meter switched on.
3) Set the constants in Setup menu according to your requirements.
4) Write the constants by selecting the Zapsat (Write) menu option.
5) Check the changes using the Nacist (Load) menu option.
6) The changes will take effect after the meter is restarted or during reinitialization.
Archives
Archives are accessible from meter's menu (see Menu structure) or by means of user software
"CALOR-40 Setup" – Data section.
Procedure for reading the archives by means of user software:
1) Remove the top cover.
2) Connect the USB cable with PC with the meter switched on.
3)Select the parameters for loading the archives according to your requirements.
4) Select the Nacist (Load) menu option to load the archives.
Note: The SYLK menu option creates an "Arch.slk" file in the existing directory compatible
with the SYLK format. This format can be opened, e.g. in Excel or any other spreadsheet.
Backup in case of total destruction of RAM memory
The billing data are backed up in several ways. The total energy data is backed up by every
saving along with daily archives. Besides this backup, all of the incremental counters
(E,V+,V-,Vin1,and Vin2 and total disable state) are backed up at a certain increment to the
so-called Crash sector. In the case of total data loss, the data can be loaded from the Crash
sector.
Loading can be performed again by means of user software "CALOR-40 Setup" – Crash
sector section.
Safety rules for operator
The operator is allowed to operate this equipment only in terms of CONTROLLINGitem.
Any interference with the induction flow sensor, resistance temperature sensors and the meter
itself by the operator are illegal and they may lead to direct scalding by the medium in the