5. Put the rear cover back. Use slight pressure to lock the snaps into the housing. Pay attention
that the cover is in correct position and not upside down!
6. Plug the modules back into the slots.
7. Power the controller on, adjust date and time and check all setpoints.
Hint:
When internal RTC battery becomes flat, controller function (e.g. Ready for standby) does not change
until controller power supply is switched off. Sometime before the battery is completely exhausted, a
warning message appears in Alarmlist: "RTCbatteryFlat".
After the next power switch on (with flat battery already) controller:
Genset is still possible to run
All new history records will have not valid date and time stamp.
Time and Date values are set not valid value
Statistics values are random
Timers (Timer1..2 Function) will not be executed
Fuel theft protection may not work