EasyManuals Logo

ComAp intelilite nt amf20 User Manual

ComAp intelilite nt amf20
145 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
InteliLite
NT
AMF20/25, SW version 2.2, ©ComAp September 2014 29
IL-NT-AMF-2.2-Reference Guide.pdf
6- Set setpoint “MCB Opens On” to MAINSFAIL on both controllers.
7- Set „DualAMFTime“ to time period in which you wish to switch gensets in supplying the load.
For example 6 hours. Make this setting on Master controller. Only Master controller controls
this timer.
8- Set "Operation Mode" to MASTER on first controller and to SLAVE on second controller.
9- Change the mode of both controllers to AUT.
10- System is now ready for DualAMF function.
Wiring of system with selectable MASTER and SLAVE role settings:
Hint:
GCB and MCB breakers feedbacks are recommended, but not required.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp intelilite nt amf20 and is the answer not in the manual?

ComAp intelilite nt amf20 Specifications

General IconGeneral
BrandComAp
Modelintelilite nt amf20
CategoryController
LanguageEnglish

Related product manuals