InteliLite
NT
AMF20/25, SW version 2.2, ©ComAp September 2014 91
IL-NT-AMF-2.2-Reference Guide.pdf
EF CT Ratio [/5A]
Earth Fault current transformer ratio.
Step: 1 A
Range: 1 2000 A /5A
EarthFault Sd [A]
Shutdown threshold level for Earth Fault current.
Step: 0,01 A
Range: 1 500 A
EarthFault Del [s]
Earth Fault current measurement delay.
Step: 0,01s
Range: 1 5s