S280-77-4
!
SAFETY
FOR LIFE
Feature ON/OFF
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
20 1 0 YES -- -- -- Sequence Coordination (ON/OFF) ON
Select Sequence Coordination ON and OFF using
the CHANGE key.
Sequence Coordination automatically advances the
control sequence one step if both of the following
conditions are met:
a. Line current exceeds the programmed minimum
trip value for a time duration shorter than the pro-
grammed control response time. No trip signal is
issued.
b. The control is programmed for at least one opera-
tion on TCC1.
Sequence Coordination will not advance the control
for those operations programmed for TCC2.
The Sequence Coordination feature operates for
both phase and ground faults; however, its program
of advancing the sequence position is controlled only
by the setting of Phase TCC1. If the control is pro-
grammed for all operations on TCC1, the sequence
coordination feature is not operative on the last oper-
ation. The feature will not advance the control if
advancing produces lockout.
If non-reclosing is activated, the Sequence Coordi-
nation feature is disabled.
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
21 1 0 YES -- -- -- Target Reset After Successful Reclose ON
(ON/OFF)
Select the Target Reset feature ON and OFF via the
CHANGE key.
Fault targets may be reset automatically after a suc-
cessful reclose (see Access Code 06) or manually
reset via the CLEAR key.
With the feature ON, targets are displayed only
when the control is in the lockout position.
With the feature OFF, targets are displayed only
after the control has initiated a trip signal indepen-
dent of any reclosing.
Phase Identification
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
17 1 0 NO -- -- -- Bushings 1-2 Phase Identifier A
18 1 0 NO -- -- -- Bushings 3-4 Phase Identifier B
19 1 0 NO -- -- -- Bushings 5-6 Phase Identifier C
Select phase target identification as A, B, C or 1, 2, 3
using the CHANGE key.
Targets are examined via Access Code 30.