Kyle Form 4C Microprocessor-Based Recloser Control Programming Guide
Features ON/OFF (cont’d)
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
22 1 0 YES -- -- -- Operations Counter (ON/OFF) ON
• With the feature ON, the total number of control trip
operations is recorded.
• Select Operations Counter ON or OFF using the
CHANGE key.
• The Operations Counter automatically returns to the
ON position when the front display is OFF.
• Control trip operations are initiated via manual oper-
ation of the pistol-grip switch on the front panel or
through automatic or supervisory operation (Access
Code 39).
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
24 1 0 YES -- -- -- Recloser Duty Monitor (ON/OFF) ON
• With feature ON, the recloser duty is recorded for
each individual phase (Access Codes 170 through
173).
• The Recloser Duty Monitor automatically returns to
the ON position when the front display is OFF.
• Select Recloser Duty Monitor ON or OFF using the
CHANGE key.
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
23 1 0 YES -- -- -- Event Recorder (ON/OFF) ON
• With the feature ON, the event recorder records event
history information of up to 50 events, including time,
date, and current levels on all three phases and
ground (Access Codes 160 through 169).
• The Event Recorder automatically returns to the ON
position when the front display is OFF.
• Select Event Recorder ON or OFF using the
CHANGE key.