39
S280-77-4
!
SAFETY
FOR LIFE
Time–Current Curve Modifiers (cont’d)
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
111 1 0 YES -- -- -- TCC2 Selection-Phase 117
111 1 0 YES -- -- -- TCC2 Selection-Ground 135
Allows the selection of a programmed, fast or
delayed, timecurrent curve to be modified. In most
situations, TCC2 is designated as a delayed or slow
curve.
Use the PHASE/GROUND key to select phase or
ground TCC2.
When TCC characteristics are modified, the readout
of Code 111 will indicate a modified curve by prefix-
ing the TCC with a lower case c.
Access Codes 111 or 03 can be used to examine
TCC2.
Changes to Access Code 111 automatically update
Access Code 03.
Changes to Access Code 03 automatically update
Access Code 111.
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
112 1 0 YES 0.20 0.00 0.01 TCC2 Constant Time Adder- 0.00*
Phase (seconds)
112 1 0 YES 0.20 0.00 0.01 TCC2 Constant Time Adder- 0.00*
Ground (seconds)
Modifies the programmed TCC2 to delay the time of
overcurrent trip.
Use with the PHASE/GROUND key to modify phase
or ground TCC2.
* Default setting when TCC2 is changed from Access
Code 03 (key 3).