40
Kyle Form 4C Microprocessor-Based Recloser Control Programming Guide
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
114 1 0 YES 42 0 1 TCC2 Minimum Response Time- 0*
Phase (cycles)
114 1 0 YES 42 0 1 TCC2 Minimum Response Time- 0*
Ground (cycles)
• Allows modification of the programmed TCC2 by
selecting a minimum response time in a range from
0 to 42 cycles.
• Use with the PHASE/GROUND key to modify phase
or ground TCC2.
* Default setting when TCC2 is changed from Access
Code 03 (key 3).
Time–Current Curve Modifiers (cont’d)
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
113 1 0 YES 2.00 0.10 0.01 TCC2 Multiplier Value-Phase 1.00*
113 1 0 YES 2.00 0.10 0.01 TCC2 Multiplier Value-Ground 1.00*
• Vertically shifts programmed TCC2 by applying a
desired multiplier.
• Use with the PHASE/GROUND key to modify phase
or ground TCC2.
* Default setting when TCC2 is changed from Access
Code 03 (key 3).