23
ver.071217-2.10
iLEARN System Manual
iLEARN Door Control Menu Screens (continued)
07 - Open Hall Button (NO)
08 - Interlock Zone - Rear (NO)
09 - EUD (NC)
10 - Interlock Zone - Front (NO)
11 - Stop Hall Button (NC)
12 - Close Hall Button (NO)
1.3.11 Door Status Bits
01 - Init – Set to ‘0’ until both iSensors have learned their stall position. Set to ‘1’ when both
have seen stall.
02 - Run – See “Motor Control Bits/Run”
03 - Reset – Set to ‘1’ when drive powers on. Set to ‘0’ upon rst door operation command.
04 - EEPROM OK – Set to ‘1’ when non-volatile memory is determined to contain good
parameter data. Set to ‘0’ when parameters are bad, and locks out operation.
05 - Fault – This is a “catchall” and is set during any fault condition (iSensor OK = ‘0’ or 6 -
Timeout = ‘1’ or EEPROM good = ‘0’)
06 - Timeout – Indicates a stall condition was not detected in the maximum time allotted (60
seconds).
07 - iSensor OK – Indicates iSensors are functioning. A ‘0’ indicates an iSensor problem.
08 - Excessive Stall Correction - Set when updated stall position exceeds 1” from the last
one.
09 - Full Close – Set when within ¾” of full close stall position.
10 - Full Open – Set when within ¾” of full open stall position.
11 - Almost Closed – Set when the door magnet is over the Close iSensor (the upper one).
12 - Almost Open – Set when the door magnet is over the Open iSensor (the lower one).