INSTALLATION MANUAL
Submersible Sump / Efuent Pump
IMPORTANT! Read all instructions in this manual before operating pump.
As a result of Crane Pumps & Systems, Inc., constant product improvement program,
product changes may occur. As such Crane Pumps & Systems reserves the right to
changeproductwithoutpriorwrittennotication.
420 Third Street 83 West Drive, Bramton
Piqua, Ohio 45356 Ontario, Canada L6T 2J6
Phone: (937) 778-8947 Phone: (905) 457-6223
Fax: (937) 773-7157 Fax: (905) 457-2650
www.cranepumps.com
Form No. 112896 - Rev. P
Series: SP50
1/2 HP, 3450 RPM, 60 Hz.

Questions and Answers

  • C
    Christine GarzaAug 1, 2025
    Why is my Crane Barnes SP50 Water Pump not delivering enough capacity?
    • M
      meghan04Aug 1, 2025
      If your Crane Water Pump is running but not delivering enough water, it could be due to several reasons. The voltage might be incorrect. The inflow may be excessive, or the pump might not be the right size for the job. There could be a restriction in the discharge line. The check valve might be stuck closed or installed backward. The shut-off valve could be closed. The impeller might be jammed, loose, worn, damaged, or have a plugged cavity or inlet. The pump could also be airlocked, or it might be running backward.
  • D
    dcookAug 5, 2025
    What to do if my Crane Barnes SP50 Water Pump will not turn off?
    • C
      Cody LewisAug 6, 2025
      If your Crane Water Pump won't turn off, several factors could be at play. The float movement might be restricted, or the switch might be defective. It's also possible that the inflow is too high, or the pump isn't properly sized for the application. The pump could be airlocked, or the H-O-A switch on the panel might be in the “HAND” position.
  • H
    Heidi MitchellAug 9, 2025
    Why does my Crane Barnes SP50 cycle too frequently?
    • K
      Karen SmithAug 9, 2025
      If your Crane Water Pump is cycling too frequently or running when not in use, the check valve might be stuck or installed backward. Fixtures could be leaking, or groundwater might be entering the basin.
  • B
    Brad JohnsonAug 14, 2025
    Why does my Crane Barnes SP50 Water Pump hum but not run?
    • D
      David FergusonAug 14, 2025
      If your Crane Water Pump is humming but not running, it could be due to incorrect voltage or the impeller being jammed or loose on the shaft. The impeller might also be worn or damaged, or its cavity or inlet could be plugged.
  • N
    Nancy GonzalezAug 18, 2025
    What to do if Crane Barnes SP50 turns on and off by itself?
    • K
      Kenneth NicholsAug 18, 2025
      If your Crane Water Pump shuts off and turns on by itself, tripping the thermal overload protector, it might be due to incorrect voltage or excessive inflow. The impeller could be jammed, loose, worn, or damaged, or its cavity or inlet could be plugged. Also, the water temperature might be too high.
  • C
    Cindy RossAug 22, 2025
    Why is my Crane Barnes SP50 so noisy?
    • J
      Jacob BrownAug 22, 2025
      If your Crane Water Pump is operating noisily or vibrating excessively, it could be due to worn bearings or a bent motor shaft. There might be debris in the impeller cavity or a broken impeller. The pump could be running backward, or the piping attachments to the building structure might be too rigid or too loose.
  • D
    Douglas MartinOct 26, 2025
    How to troubleshoot Crane Barnes SP50 Water Pump that will not run?
    • W
      William ValdezOct 26, 2025
      If your Crane Water Pump isn't running, start by checking all electrical connections to ensure they are secure. An electrician can measure the current in the motor leads. If the current is within ±20% of locked rotor Amps, the impeller is likely locked. If the current reads 0, the overload might be tripped; in this case, remove power, let the pump cool down, and then recheck the current. Also, ensure the liquid level is at least at the suggested turn-on point and recheck all sizing calculations to determine the proper pump size. Check the discharge line for any restrictions, including ice if the line runs through cold areas. Remove and inspect the check valve for correct installation and free operation. Open the valve, check the impeller for free movement, security, and condition, and clea...

Summary

Barnes Installation Manual Overview

Safety First! Important Warnings

General Safety Precautions

Key symbols and general safety warnings for pump installation and operation.

Electrical Safety Guidelines

Precautions regarding electrical shock, grounding, and wiring.

Pump Specifications

Pump Installation Guidelines

Service and Repair Procedures

Troubleshooting Pump Issues

Pump Not Running or Turning Off

Diagnosing issues related to the pump not starting or not stopping.

Pump Performance Problems

Troubleshooting insufficient capacity, frequent cycling, and noisy operation.

Overload Protector Trips

Addressing the cause of the thermal overload protector tripping the pump.

Crane Barnes SP50 Series Specifications

General IconGeneral
Impeller MaterialThermoplastic
PhaseSingle
Horsepower0.5 HP
Voltage115V
MaterialThermoplastic
SeriesSP50 Series