How to fix Crane PROSSER HYMERGIBLE 7-06000 that delivers insufficient capacity?
- EEileen PhelpsAug 31, 2025
To address a Crane Water Pump delivering insufficient capacity, consider the following: * Check and correct low supply pressure/flow. * Recheck sizing calculations to ensure the pump is appropriately sized. * Inspect the discharge line for restrictions, including ice. * Examine the check valve for proper installation and operation. * Ensure the shut-off valve is open. * Inspect the impeller for obstructions, damage or operational issues. Clean impeller and inlet of any obstruction. * Address potential airlocks by loosening the union and cleaning the vent hole. * Verify correct pump rotation. * Repair any piping leaks.