EasyManua.ls Logo

Crestron Cresnet Network - Page 23

Crestron Cresnet Network
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Design Guide Doc. 9292A Cresnet® Network 19
NOTE:If Crestron certified wire and cable is not used and technical onsite support is
required to troubleshoot an issue caused by improper wiring, a support charge may be
incurred.
l
To maintain data integrity, Cresnet cable lengths should not exceed 1,500 ft (457 m)per
run.
l
While not mandatory, Crestron recommends placing service loops within Cresnet wiring
runs for future accessibility.
l
When daisy chaining network units, always twist the ends of the incoming wire and
outgoing wire that share a pin on the network connector.
o
Do not twist the white and blue wires together. Only twist the copper strands on the
end of each individual wire.
o
The compression connector requires the strands of each wire to compress down to
hold the wire correctly during temperature changes.
l
Observe the following when grounding the data twisted pair drain wire:
o
Stranded drain wire is connected at the power supply end only.
o
Foil shield can be removed at both ends.
l
When terminating multiple wires into a green (3.5mm) terminal block:
o
Never use more than one 18AWG(0.82mm
2
) or one 12 AWG(3.31mm
2
) wires in the
same pin connection.
o
Never use more than two 22AWG(0.33mm
2
) wires in the same pin connection.
l
When terminating multiple wires into a black (5mm) terminal block:
o
Never use more than two 18AWG(0.82mm
2
) or one 12 AWG(3.31mm
2
) wires in
the same pin connection.
o
Never use more than two 22AWG(0.33mm
2
) wires in the same pin connection.
l
Following termination:
o
Ensure that each cable and its corresponding wire strands are not frayed or
touching any other connection on the connector.
o
Copper wire should be barely visible.
o
Wires should not be able to be removed from the connector when applying 5N (or
less)of force.
o
Heat shrink can be used to cover the PVCjacket transition to the four wires to allow
for additional strain relief.
o
Labels should be applied to match any applicable drawings or labeling practices
used within the Cresnet installation.