Design Guide Doc. 9292A Cresnet® Network 25
NOTE:Cresnet Yand Zdata must use one twisted pair. Using one twisted pair for Cresnet Y
and another twisted pair for Cresnet Z can cause too much resistance.
Poor Wiring
All wired connections should be checked to ensure that all wiring has been properly stripped and
terminated to the connector.
l
Many network issues are caused by loose wire strands that can short another pin or
missing wire strands.
l
If any loose or missing wire strands are discovered, redress the connection. Also, ensure
that all screws on the terminal block are tightened down to the wires.
Excessive Cresnet Clients
No more than 25 Cresnet clients can be powered by a single Cresnet server. If more than 25
Cresnet clients are required, use a Cresnet hub or Ethernet-to-Cresnet bridge to add additional
devices to the Cresnet network.