Product Manual — Doc. 9239A GLS-OIR-CSM-EX-BATT • 19
Test Mode
Test mode allows the GLS-OIR-CSM-EX-BATT to be tested to ensure that the sensor is triggered
by the proper amount of motion. It also allows for the RF ID and firmware to be updated more
efficiently.
To enter Test mode, hold the TEST button for 4 seconds. The green LED flashes to indicate the
device is powered and has entered Test mode.
When the device is in Test mode, the green LED flashes once to indicate that initial motion has
been detected. The red LED lights when motion is detected and stays lit if continuous motion is
sensed. Timeout settings do not take effect and no information is sent to the control system
during Test mode. After final vacancy is detected, the green LED flashes once.
The sensor exits Test mode once the TEST button is pressed again or after 5 minutes. When
exiting Test mode, the sensor’s green LED flashes. When the sensor exits Test mode, it enters
Light Sleep mode. When in Light Sleep mode, the sensor checks for updates from the control
system (such as new firmware or RF ID changes) every 30 seconds.
NOTE: When the GLS-OIR-CSM-EX-BATT is in Test mode, all the Light Sleep mode
functionality is available.
Set the RF ID
It is recommended to have direct access to the GLS-OIR-CSM-EX-BATT and to use Crestron
Toolbox™ to set the RF ID of the device. To set the RF ID:
1. Wake the device by pressing the TEST button.
2. Set the RF ID of the device using Crestron Toolbox. The RF ID must match the RF ID
specified in the Crestron Studio™ or SIMPL Windows program.
3. Press the TEST button on the GLS-OIR-CSM-EX-BATT to ensure that the device is still
awake and the RF ID is transferred to the device.
The RF ID can also be set by placing the device into TEST mode:
1. Press the TEST button for more than 4 seconds. The LED flashes.
2. Set the RF ID using Crestron Toolbox. Setup mode is exited after 5 minutes.
When the sensor is acquired by a gateway, it checks for RFIDupdates from the control system
for 60 minutes.