AV
0
Analog in 0
Read Only No
Percentage
AV
1
Analog in 1 Read Only No
Percentage
AV
2
Analog in 2
Read Only No
Percentage
AV
3 Analog in 3
Read Only
No
Percentage
AV
4
In Use Set Point
Read / Write
YES
AV
5
Current Air Flow / Velocity
Read Only
No
AV
6
Standby Set Point Read / Write YES
AV 7 Current CFM Read Only No
CFM
AV 8 Current Sash Area Read Only No
Inches
AV 9 Mode Read / Write No
AV 10
Condition Read Only No
0 = Hood Normal, 1 = Caution, 2 = Alarm
AV
11
Alarm High
Read / Write Yes
AV
12 Alarm Low
Read / Write Yes
AV 13
Pass Through CFM IN Read Only No
Summed CFM from other hoods
AV
14 Current Sash Open Percent
Read Only No
AV 15 K Factor
Read / Write Yes
AV 16 Valve Sensor High Read / Write
Yes
Inches WC
AV 17 Valve Sensor Low Read / Write Yes
Inches WC
AV 18 P Gain Read / Write Yes
AV 19 I Gain Read / Write Yes
AV 20 Min Flow Read / Write Yes
AV 21 Max Fl ow Read / Write Yes
AV 22 Sash Alarm Status Read Only No
0= no alarm, 1 = alarm, 2 = alarm mute
AV 23 Control Output (PID Output) Read Only No
Percentage
AV 24 Current "WC Read Only No
Inches WC
AV 25 Total CFM Out Read Only No
Summed CFM from this and other hoods
AV 26 Sash Open SqFt - (CRC-SVS usage only) Read Only No
Derives value from face velocity and volume
AV 27 Sash Open % - (CRC-SVS usage only) Read Only No
Derives value from face velocity and volume
BV 0 Digital Input 1 Read No
BV 1 Digital Input 2 Read No
BV 2 Digital Input 3 Read No
BV 3 Digital Input 4 Read No
BV 4 Sash Area Alarm - No delay Read No
0 = no alarm, 255 (FF) = alarm
BV 5 Audible Alarm Read / Write No
0 = no alarm, 255 (FF) = alarm - Write 0 to mute