29
Appendix: Approximate Back-up Time Table
Model Load (VA) Load (W) Backup Time @ 24Vdc 100Ah (min) Backup Time @ 24
Vdc 200Ah
(min)
X-3KVA-M
300 240 449 1100
600 480 222 525
900 720 124 303
1200 960 95 227
1500 1200 68 164
1800 1440 56 126
2100 1680 48 108
2400 1920 35 94
2700 2160 31 74
3000 2400 28 67
Note: Backup time depends on the quality of the battery, age of battery and type of battery.
Specifications of batteries may vary depending on different manufacturers.